6.3 Network Range Assignment
6.3.6 Supplementary settings
6
PARAMETER SETTING
(3) Punctuality is guaranteed.
Set whether or not to assure the punctuality. (Default: Punctuality is guaranteed.)
If the [Punctuality is guaranteed] checkbox is checked, each station sends transient
transmissions for the number of times specified in [Maximum No. of transients in one
station], which keeps the link scan time constant.
For details, refer to the following.
Section 4.1.6 Cyclic transmission punctuality assurance
The following describes the link scan operation varied depending on whether the
punctuality is assured or not.
(4) Maximum No. of transients in one station.
Set the number of transient transmissions that one station can perform in one link
scan.
(Setting range: 1 to 10 times, Default: 2 times)
Table 6.14 Link scan operation varied depending on whether the punctuality is assured or not
Punctuality
assurance
Link scan operation
Punctuality is
guaranteed.
• Link scan time is kept constant.
• Link scan time is longer compared to the case where "Punctuality is not guaranteed".
• Link scan time increases as the value set in [Maximum No. of transients in one
station] increases.
Punctuality is not
guaranteed.
• Link scan time will vary when transient transmission is requested.
• The variation in link scan time increases as the value set in [Maximum No. of
transients in one station] increases.