10
- 22
10.2 Error Code List
10
TROUBLESHOOTING
E2A3
H
Frame length (L) error
An invalid transient frame was
received from a CC-Link IE controller
network compatible device.
• Check the contents of the transient frame on the
sending end.
For details, please consult the manufacturer of
the CC-Link IE controller network compatible
device.
E2A4
H
Gate count (GCNT) error
E2A5
H
Destination address (DA) error
E2A6
H
Source address (SA) error
E2A7
H
Destination application type
(DAT) error
E2A8
H
Source application type (SAT)
error
E2A9
H
Destination network No.
(DNA) error
E2AA
H
Destination address (DS) error
E2AB
H
Source network No. (SNA)
error
E2AC
H
Source address (SS) error
E2AD
H
Data length (L1) error
E2AE
H
Target specification error
E2AF
H
Target station No. error
(CC-Link dedicated
instruction)
The own station No. was set as the
target station No.
• Confirm the target station No. in the control data,
and retry the operation.
• If the error persists even after taking the above
action, please consult your local Mitsubishi
representative.
E2B0
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
E300
H
to
E302
H
E310
H
E311
H
E320
H
to
E325
H
E330
H
to
E333
H
E340
H
to
E343
H
E350
H
E361
H
to
E36D
H
E380
H
to
E383
H
E390
H
to
E397
H
E3A0
H
E3A1
H
E3B0
H
to
E3BA
H
E3BB
H
Max. number of stations
exceeded
The total number of stations
exceeded the setting range.
• Assign some stations to another network so that
the total number of stations will be within the
setting range.
Table 10.1 Error Code List (Continued)
Error code
Error
Error detail
Corrective action