5
- 26
5.6 Tests for CC-Link IE controller network Startup
5.6.2 Station-to-station test
5
PREPARATION AND SETUP
5.6.2
Station-to-station test
Station-to-station test checks the condition of the cable connected between two stations
(from OUT of the executing station to IN of the other station.)
(1) System configuration and parameter setting for other than redundant
systems
(a) System configuration
1) Connect GX Developer to the CPU module.
2) Turn OFF the power and connect an optical fiber cable between OUT of the
executing station and IN of the other station.
3) Turn ON the power.
(b) Setting network parameters in GX Developer
1) Set the test-executing station to Test between station mode.
After setting the following network parameters in GX Developer, write them to
the programmable controller.
Figure 5.30 System configuration
Figure 5.31 Network parameters in GX Developer
Table 5.11 Network parameter setting items of GX Developer
Item
Set value
Network type
CC IE Control (Control station)
Starting I/O No.
0000
Network No.
1
Total stations
4
Group No.
0
Station No.
1
Mode
Test between station
Station-to-station test
(executing station)
Control station
No.1
Station-to-station test
(target station)
Normal station
No.2
GX Developer