9
DEDICATED INSTRUCTIONS
9.7 J(P)/G(P).REQ (Remote RUN/STOP)
9
- 55
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
(S1)+5
Target station No.
Specify the station No. of the target station.
(1) Station No. specification
When own station is Universal model QCPU: 1 to 120
When own station is other than Universal model QCPUs: 1 to 64
(2) Group
81
H
to A0
H
: All stations in group No.1 to 32
(3) All stations
FF
H
: All stations of the target network No. (Except the own
station)
To specify a group or all stations, set "0000
H
" or "03FF
H
" for Target
station's CPU type (S1+3). (
1 to 120
81
H
to A0
H
FF
H
User
(S1)+6
—
Unused
0
User
(S1)+7
Number of resends
1) For instruction execution
Specify the number of times the instruction is to be resent when it
is not completed within the monitoring time specified in (S1)+8.
0 to 15
User
2) At instruction completion
The number of resends executed (result) is stored.
—
System
(S1)+8
Arrival monitoring
time
Specify the monitoring time required for instruction completion.
If an instruction is not completed within this time, it will be resent the
number of times specified in (S1)+7.
0: 10 seconds
1 to 32767: 1 to 32767 seconds
0 to 32767
User
(S1)+9
Request data
length
Specify the request data size (words)
(Number of words of the request data to be stored in the own station's
start device (S2))
4: Remote RUN
3: Remote STOP
3, 4
User
(S1)+10
Response data
length
The response data size (words) is stored.
(Number of words of the response data to be stored in the own
station's start device (D1))
2: Remote RUN/STOP
—
System
(S1)+11
Clock set flag
*2
The valid or invalid status of the data in the area starting from (S1)+12
is stored.
0: Invalid
1: Valid
—
System
(S1)+12
to
(S1)+15
Clock data on error
completion
*2
Clock data on error completion are stored in BCD format.
When the target station is QnACPU, "00
H
" is stored in the Year field
(first two digits of the year).
—
System
Table 9.26 Control data (Continued)
Device
Item
Setting data
Setting range
Setting
side
*1
Group No.1 81
H
Group No.2 82
H
Group No.32 A0
H
(S1)+12
(S1)+13
(S1)+14
(S1)+15
Month (01
H
to 12
H
)
Hour (00
H
to 23
H
)
Second (00
H
to 59
H
)
Day (01
H
to 31
H
)
Minute (00
H
to 59
H
)
00
H
(Sun.) to 06
H
(Sat.)
Day of week (00
H
to 06
H
)
Year (00
H
to 99
H
) First 2 digits
Year (00
H
to 99
H
) Last 2 digits
b15
b8 b7
to
b0
to