SB0033
RECV execution
request flag (4)
Stores the data reception status of channel 4 of the own station.
OFF: No data reception
ON: Data received
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error are held.
SB0034
RECV execution
request flag (5)
Stores the data reception status of channel 5 of the own station.
OFF: No data reception
ON: Data received
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error are held.
SB0035
RECV execution
request flag (6)
Stores the data reception status of channel 6 of the own station.
OFF: No data reception
ON: Data received
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error are held.
SB0036
RECV execution
request flag (7)
Stores the data reception status of channel 7 of the own station.
OFF: No data reception
ON: Data received
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error are held.
SB0037
RECV execution
request flag (8)
Stores the data reception status of channel 8 of the own station.
OFF: No data reception
ON: Data received
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error are held.
SB0040
Network type (own
station)
Stores the network type of own station.
OFF: Controller network
SB0041
Host station's
redundant function
support information
Stores the redundant system information of the CC-Link IE controller network
module on the own station.
OFF: Redundant function not supported
ON: Redundant function supported
Table App.2 Link special relay (SB) list (Continued)
No.
Name
Description
Availability
Control
station
Normal
station
Link special relay (SB): SB0033 to SB0041
Содержание QJ71GP21-SX
Страница 1: ......
Страница 2: ......
Страница 644: ...App 94 Appendix 6 External Dimensions Appendix 6 2 QJ71GP21S SX APPENDICES Memo ...
Страница 649: ......
Страница 650: ......