9
- 36
9.5 JP/GP.WRITE
9
DEDICATED INSTRUCTIONS
(3) Function
(a) WRITE instruction overview
The WRITE instruction writes word device data (in and after (S2)) of the own
station to word devices of the target station (in and after (D1)).
The target station is specified in Target station network No. ((S1)+4) and Target
station No. ((S1)+5) of control data.
Upon completion of writing data to the target station devices, Completion device
(D2) turns ON.
(b) Target stations available for specification
1) Target network
In addition to CC-Link IE controller network, stations in the following networks
can be also specified.
• MELSECNET/H
• MELSECNET/10
• Ethernet
2) Target station's CPU type
The WRITE instruction is executable only when the target station has QCPU or
QnACPU.
The WRITE instruction is not executable to the ACPU connected to
MELSECNET/10 or Ethernet.
Figure 9.31 WRITE instruction
Channel 1
Channel n
Channel 10
WRITE
CC-Link IE controller
network module
CPU module
CPU module
Network
module
(S2)
(D1)
[Own station]
[Target station]