10.1 Troubleshooting Flow
10.1.6 Cyclic transmission is disabled
10
TROUBLESHOOTING
Figure 10.7 When cyclic transmission is disabled (Continued)
Checking
own station
(sending side)
Checking
other station
(receiving side)
STOP/RESET
ON
RUN
Yes
Yes
Yes
No
No
No
Check the sequence program
(for overwriting of data).
Is B/W value changed?
Is LB/LW value changed?
Monitor the B/W by device batch monitor of
GX Developer.
Check the sequence program.
(See if data write destination is correct.)
Is LB/LW value changed?
Is the CPU module of own or
another station set to RUN?
Set the CPU modules of own station and other
station to STOP.
End
Change B/W value by device test of GX Developer.
Monitor the LB/LW (J \ ) by device batch monitor
of GX Developer.
Monitor the LB/LW (J \ ) by device batch monitor
of GX Developer.
Check the refresh parameter. (See if assignment
is not wrong or CPU-side device is not duplicated.)
Check the refresh parameter. (See if assignment
is not wrong or CPU-side device is not duplicated.)
For relay station, check to see if link refresh range
and transfer target link device range (interlink
transmission parameter) are not duplicated.
Check each station send range with
[Network range assignment] of control station.
Check each station send range with [Network
range assignment] of control station.
Set the CPU module to RUN.
1)
Section 6.3 Network Range Assignment
Section 6.4 Refresh Parameters
Section 6.7 Interlink Transmission Parameters