Chapter 9: Using the Command Line Interface
630
Changing an Outlet's Default State
This section applies to outlet-switching capable models only.
This command determines the initial power condition of an outlet after the
PX3TS powers up.
config:#
outlet <n> stateOnDeviceStartup <option>
Variables:
•
<n> is the number of the outlet that you want to configure.
•
<option> is one of the options:
off
,
on,
lastKnownState
and
pduDefined.
Option
Description
off
Turn off the outlet.
on
Turn on the outlet.
lastKnownState
Restore the outlet to the state prior to last PDU power
down.
pduDefined
PDU-defined setting.
Note: Setting the outlet's default state to an option other than
pduDefined
overrides the PDU-defined default state on that outlet. See
Setting the
PDU-Defined Default Outlet State
(on page 571).
Summary of Contents for Raritan PX3TS
Page 4: ......
Page 6: ......
Page 20: ......
Page 80: ...Chapter 4 Connecting External Equipment Optional 60...
Page 109: ...Chapter 5 PDU Linking 89...
Page 117: ...Chapter 5 PDU Linking 97...
Page 441: ...Chapter 7 Using the Web Interface 421...
Page 464: ...Chapter 7 Using the Web Interface 444...
Page 465: ...Chapter 7 Using the Web Interface 445 Continued...
Page 746: ...Appendix A Specifications 726...
Page 823: ...Appendix I RADIUS Configuration Illustration 803 Note If your PX3TS uses PAP then select PAP...
Page 828: ...Appendix I RADIUS Configuration Illustration 808 14 The new attribute is added Click OK...
Page 829: ...Appendix I RADIUS Configuration Illustration 809 15 Click Next to continue...
Page 860: ...Appendix J Additional PX3TS Information 840...
Page 890: ...Appendix K Integration 870 3 Click OK...
Page 900: ......