Chapter 9: Using the Command Line Interface
669
Example - Default Upper Thresholds for Temperature
It is assumed that your preferred measurement unit for temperature is set to
degrees Celsius. Then the following command sets the default Upper Warning
threshold to 20
and Upper Critical threshold to 24
for all temperature
sensors.
config:#
defaultThresholds temperature upperWarning 20
upperCritical 24
Sensor Threshold Configuration Commands
A sensor configuration command begins with
sensor
. You can use the
commands to configure the threshold, hysteresis and assertion timeout values
for any sensor associated with the following items:
▪
Inlets
▪
Outlets (only available for models with outlet switching)
▪
Overcurrent protectors
▪
Environmental sensors
▪
Transfer switch sensors
It is permitted to assign a new value to the threshold at any time regardless of
whether the threshold has been enabled.
Commands for Inlet Sensors
A sensor configuration command for inlets begins with
sensor inlet
.
You can configure various inlet sensor threshold settings at a time by
combining multiple commands. See
Multi-Command Syntax
(on page 695).
Set the Upper Critical threshold for an inlet sensor:
config:#
sensor inlet <n> <sensor type> upperCritical <option>
Set the Upper Warning threshold for an inlet sensor:
config:#
sensor inlet <n> <sensor type> upperWarning <option>
Set the Lower Critical threshold for an inlet sensor:
Summary of Contents for Raritan PX3TS
Page 4: ......
Page 6: ......
Page 20: ......
Page 80: ...Chapter 4 Connecting External Equipment Optional 60...
Page 109: ...Chapter 5 PDU Linking 89...
Page 117: ...Chapter 5 PDU Linking 97...
Page 441: ...Chapter 7 Using the Web Interface 421...
Page 464: ...Chapter 7 Using the Web Interface 444...
Page 465: ...Chapter 7 Using the Web Interface 445 Continued...
Page 746: ...Appendix A Specifications 726...
Page 823: ...Appendix I RADIUS Configuration Illustration 803 Note If your PX3TS uses PAP then select PAP...
Page 828: ...Appendix I RADIUS Configuration Illustration 808 14 The new attribute is added Click OK...
Page 829: ...Appendix I RADIUS Configuration Illustration 809 15 Click Next to continue...
Page 860: ...Appendix J Additional PX3TS Information 840...
Page 890: ...Appendix K Integration 870 3 Click OK...
Page 900: ......