Appendix J: Additional PX3TS Information
843
Multi-phase inlets or outlets:
•
Line-Line RMS voltage:
Threshold
Default value
Lower critical
-6% of minimum rating
Lower warning
-3% of minimum rating
Upper warning
+3% of maximum rating
Upper critical
+6% of maximum rating
Hysteresis
2V
•
Line RMS current:
Threshold
Default value
Upper warning
65% of rating
Upper critical
80% of rating
Hysteresis
1A
•
Unbalanced current:
Threshold
Default value
Upper critical
10% -- disabled by default
Upper warning
5% -- disabled by default
Hysteresis
2%
Overcurrent protectors which aims to protect the PDU's outlets:
•
OCP RMS current:
Threshold
Default value
Upper critical
80% of OCP rating
Upper warning
65% of OCP rating
Hysteresis
1A
Summary of Contents for Raritan PX3TS
Page 4: ......
Page 6: ......
Page 20: ......
Page 80: ...Chapter 4 Connecting External Equipment Optional 60...
Page 109: ...Chapter 5 PDU Linking 89...
Page 117: ...Chapter 5 PDU Linking 97...
Page 441: ...Chapter 7 Using the Web Interface 421...
Page 464: ...Chapter 7 Using the Web Interface 444...
Page 465: ...Chapter 7 Using the Web Interface 445 Continued...
Page 746: ...Appendix A Specifications 726...
Page 823: ...Appendix I RADIUS Configuration Illustration 803 Note If your PX3TS uses PAP then select PAP...
Page 828: ...Appendix I RADIUS Configuration Illustration 808 14 The new attribute is added Click OK...
Page 829: ...Appendix I RADIUS Configuration Illustration 809 15 Click Next to continue...
Page 860: ...Appendix J Additional PX3TS Information 840...
Page 890: ...Appendix K Integration 870 3 Click OK...
Page 900: ......