Chapter 6: Using the PX3TS
109
Number
Event
Power failure
Automatic power transfer
There are three types of power transfer mechanisms:
•
Automatic transfer
•
Automatic retransfer
•
Manual transfer
Tip: You can monitor the power quality of each inlet or the power transfer
status by observing the Inlet Power indicator lamps. See
Transfer Switch
Indicator Lamps
(on page 114).
Automatic Transfer
Power is automatically transferred from the preferred inlet to the alternate
because:
•
The preferred inlet's power fails, or
•
The preferred inlet's power quality (voltage or frequency) enters the
critical level.
Power quality is indicated through the Power Quality indicator lamps. See
Power Quality Indicator Lamps
(on page 116).
The table below indicates which inlet the PX3TS selects when the power quality
changes.
Inlet power quality
Active inlet
Preferred
Alternate
Normal
Normal
Warning
Critical
Preferred
Warning
Warning
Critical
Preferred
Warning
Normal
Preferred
Critical
Normal
Warning
Alternate
Critical
Critical
None
Summary of Contents for Raritan PX3TS
Page 4: ......
Page 6: ......
Page 20: ......
Page 80: ...Chapter 4 Connecting External Equipment Optional 60...
Page 109: ...Chapter 5 PDU Linking 89...
Page 117: ...Chapter 5 PDU Linking 97...
Page 441: ...Chapter 7 Using the Web Interface 421...
Page 464: ...Chapter 7 Using the Web Interface 444...
Page 465: ...Chapter 7 Using the Web Interface 445 Continued...
Page 746: ...Appendix A Specifications 726...
Page 823: ...Appendix I RADIUS Configuration Illustration 803 Note If your PX3TS uses PAP then select PAP...
Page 828: ...Appendix I RADIUS Configuration Illustration 808 14 The new attribute is added Click OK...
Page 829: ...Appendix I RADIUS Configuration Illustration 809 15 Click Next to continue...
Page 860: ...Appendix J Additional PX3TS Information 840...
Page 890: ...Appendix K Integration 870 3 Click OK...
Page 900: ......