Chapter 9: Using the Command Line Interface
672
Sensor type
Description
residualDCCurrent
RCM DC current sensor - detects residual DC
current only.
Available only on PDUs with RCM Type B.
Note: For information on RCM Type A and B sensors, see RCM Current Sensor.
Commands for Outlet Sensors
A sensor configuration command for outlets begins with
sensor outlet
.
You can configure various outlet sensor threshold settings at a time by
combining multiple commands. See
Multi-Command Syntax
(on page 695).
Set the Upper Critical threshold for an outlet sensor:
config:#
sensor outlet <n> <sensor type> upperCritical <option>
Set the Upper Warning threshold for an outlet sensor:
config:#
sensor outlet <n> <sensor type> upperWarning <option>
Set the Lower Critical threshold for an outlet sensor:
config:#
sensor outlet <n> <sensor type> lowerCritical <option>
Set the Lower Warning threshold for an outlet sensor:
config:#
sensor outlet <n> <sensor type> lowerWarning <option>
Set the deassertion hysteresis for an outlet sensor:
config:#
sensor outlet <n> <sensor type> hysteresis <hy_value>
Set the assertion timeout for an outlet sensor:
Summary of Contents for Raritan PX3TS
Page 4: ......
Page 6: ......
Page 20: ......
Page 80: ...Chapter 4 Connecting External Equipment Optional 60...
Page 109: ...Chapter 5 PDU Linking 89...
Page 117: ...Chapter 5 PDU Linking 97...
Page 441: ...Chapter 7 Using the Web Interface 421...
Page 464: ...Chapter 7 Using the Web Interface 444...
Page 465: ...Chapter 7 Using the Web Interface 445 Continued...
Page 746: ...Appendix A Specifications 726...
Page 823: ...Appendix I RADIUS Configuration Illustration 803 Note If your PX3TS uses PAP then select PAP...
Page 828: ...Appendix I RADIUS Configuration Illustration 808 14 The new attribute is added Click OK...
Page 829: ...Appendix I RADIUS Configuration Illustration 809 15 Click Next to continue...
Page 860: ...Appendix J Additional PX3TS Information 840...
Page 890: ...Appendix K Integration 870 3 Click OK...
Page 900: ......