Chapter 9: Using the Command Line Interface
679
Example 1 - Upper Critical Threshold for a Temperature Sensor
The following command sets the Upper Critical threshold of the environmental
"temperature" sensor with the ID number 2 to 40 degrees Celsius. It also
enables the upper critical threshold if this threshold has not been enabled yet.
config:#
sensor externalsensor 2 temperature upperCritical 40
Example 3 - Upper Thresholds for Overcurrent Protector Sensors
The following command sets both the Upper Critical and Upper Warning
thresholds for the 2nd overcurrent protector.
config:#
sensor ocp 2 current upperWarning enable upperCritical 16
Results:
•
The Upper Critical threshold for the 2nd overcurrent protector's RMS
current is set to 16A. It also enables the upper critical threshold if this
threshold has not been enabled yet.
•
The Upper Warning threshold for the 2nd overcurrent protector's RMS
current is enabled.
Summary of Contents for Raritan PX3TS
Page 4: ......
Page 6: ......
Page 20: ......
Page 80: ...Chapter 4 Connecting External Equipment Optional 60...
Page 109: ...Chapter 5 PDU Linking 89...
Page 117: ...Chapter 5 PDU Linking 97...
Page 441: ...Chapter 7 Using the Web Interface 421...
Page 464: ...Chapter 7 Using the Web Interface 444...
Page 465: ...Chapter 7 Using the Web Interface 445 Continued...
Page 746: ...Appendix A Specifications 726...
Page 823: ...Appendix I RADIUS Configuration Illustration 803 Note If your PX3TS uses PAP then select PAP...
Page 828: ...Appendix I RADIUS Configuration Illustration 808 14 The new attribute is added Click OK...
Page 829: ...Appendix I RADIUS Configuration Illustration 809 15 Click Next to continue...
Page 860: ...Appendix J Additional PX3TS Information 840...
Page 890: ...Appendix K Integration 870 3 Click OK...
Page 900: ......