AKD PDMM User Guide | 6.1 Power
6.1 Power
6.1.1 Drive Setup for Power and Bus
The
Power
screen allows you to confirm Power Bus settings and accommodates external regeneration
needs if required. Nothing is required for this screen if you have no regeneration requirements. Review the
data on the screen to be certain the bus voltage is at the appropriate levels you expect (approximate input
line AC voltage * 1.4). The other values are the appropriate limits for over voltage and under voltage for the
particular drive. You can select the undervoltage fault mode to trigger either only when the drive is enabled
or always.
From the
Power
screen, you can view and configure the drive power settings as follows:
Button or Dialog
Box
Description
Parameter
Measured Bus
Voltage
Reads the current DC bus voltage.
Over Voltage
Fault Level
Reads the over voltage fault level.
Under Voltage
Fault Level
Reads the under voltage fault level.
Under Voltage
Fault Mode
Sets under voltage mode.
Operating Volt-
age
Sets the operating voltage.
Regen Resistor
Type
Sets the regen resistor type to either -
1-External Regen
or
0-
Internal Regen (if available)
.
Regen Power
Reads the regen power (only visible for external regen).
External Regen
Resistance
Sets the external, user-defined regen resistor resistance
(only visible for external regen).
External Regen
Heat Up Time
Sets the external regen resistor thermal protection time con-
stant (only visible for external regen).
External Regen
Power
Sets the regen resistor's power fault level for an external
regen resistor (only visible for external regen).
See Regeneration (pg 36) for more information about regen resistors and sizing regen resistors.
6.1.1.1 Operating Voltage
Operating voltage can be selected by the user to allow AKD PDMM-xxx07 (480Vac) drives to work on
240Vac input supplies.
The VBUS.HALFVOLT parameter has an effect on the following voltage-thresholds:
l
DC-bus over-voltage threshold (see VBUS.OVFTHRESH (pg 445)).
l
The regen-resistor enable/disable voltage thresholds.
l
The inrush-relay enable/disable voltage thresholds.
A power-cycle is needed after changing the value and saving the parameter on the NV memory of the
Drive, since the voltage thresholds mentioned above are read during the boot-sequence of the Drive.
6.1.1.2 Direct DC Mains Operation
Direct DC input is available on all standard AKD PDMM models. The DC input should be run into the AC
input connection. Positive and negative DC lines should use L1 and L2 connections (polarity is not crit-
ical). L1 and L2 connections are found on either the X3 connector or the X4 connector depending on the
model.
34
Kollmorgen™ | December 2012
Summary of Contents for AKD PDMM series
Page 25: ...This page intentionally left blank 25 Kollmorgen December 2012...
Page 32: ...This page intentionally left blank 32 Kollmorgen December 2012...
Page 52: ...This page intentionally left blank 52 Kollmorgen December 2012...
Page 101: ...AKD PDMM User Guide 12 3 6 2 Biquad Calculations 101 Kollmorgen December 2012...
Page 133: ...This page intentionally left blank 133 Kollmorgen December 2012...
Page 158: ...AKD PDMM User Guide 17 Connection Diagrams Kollmorgen December 2012 158...
Page 470: ...AKD PDMM User Guide 48 27 VL THRESH 1 Velocity Loop 470 Kollmorgen December 2012...
Page 511: ...This page intentionally left blank 511 Kollmorgen December 2012...
Page 513: ...This page intentionally left blank 513 Kollmorgen December 2012...