Name
Type
Description
OUT11
BOOLEAN
Output 11
OUT12
BOOLEAN
Output 12
OUT13
BOOLEAN
Output 13
OUT14
BOOLEAN
Output 14
OUT15
BOOLEAN
Output 15
OUT16
BOOLEAN
Output 16
15.12.5
Setting parameters
ABBD8E242451 v3
The function does not have any parameters available in local HMI or Protection and Control IED
Manager (PCM600)
15.12.6
Operation principle
SEMOD158385-4 v4
With integer 15 on the input INP the OUT1 = OUT2 = OUT3= OUT4 =1 and the remaining OUTx = 0
for (5≤x≤16).
OUTx represents a value when activated. The value of each of the OUTx is in accordance with the
table IB16_1. When not activated the OUTx has the value 0.
In the above example when integer 15 is on the input INP the OUT1 has a value =1, OUT2 has a value
=2, OUT3 has a value =4 and OUT4 has a value =8. The sum of these OUTx is equal to 1 + 2 + 4 + 8 =
15.
This follows the general formulae: The sum of the values of all OUTx = 2
x-1
where 1≤x≤16 will be
equal to the integer value on the input INP.
The Integer to Boolean 16 conversion function (IB16) will transfer an integer with a value between 0
to 65535 connected to the input INP to a combination of activated outputs OUTx where 1≤x≤16.
The sum of the values of all OUTx will then be equal to the integer on input INP. The values of the
different OUTx are according to the table below. When an OUTx is not activated, its value is 0.
When all OUTx where 1≤x≤16 are activated that is = Boolean 1 it corresponds to that integer 65535
is connected to input INP. The IB16 function is designed for receiving the integer input locally. If
the BLOCK input is activated, it will freeze the logical outputs at the last value.
Values of each of the different OUTx from function block IB16 for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on the
function block IB16.
Name of OUTx
Type
Description
Value when activated Value when
deactivated
OUT1
BOOLEAN
Output 1
1
0
OUT2
BOOLEAN
Output 2
2
0
OUT3
BOOLEAN
Output 3
4
0
OUT4
BOOLEAN
Output 4
8
0
OUT5
BOOLEAN
Output 5
16
0
Table continues on next page
1MRK 502 066-UUS B
Section 15
Logic
991
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...