18.13.2
Functionality
GUID-759CB016-2B4D-4D98-82E1-592044983D53 v2
GOOSEMVRCV is used to receive measured value using IEC61850 protocol via GOOSE.
18.13.3
Function block
GUID-A0B333CC-AEF4-40EA-B152-364648AB78D3 v1
IEC10000251-1-en.vsd
GOOSEMVRCV
BLOCK
^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251 V1 EN-US
Figure 612: GOOSEMVRCV function block
18.13.4
Signals
PID-2530-INPUTSIGNALS v18
Table 916: GOOSEMVRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
PID-2530-OUTPUTSIGNALS v18
Table 917: GOOSEMVRCV Output signals
Name
Type
Description
MVOUT
REAL
Measurand value output
DATAVALID
BOOLEAN
Data valid for measurand value output
COMMVALID
BOOLEAN
Communication valid for measurand value output
TEST
BOOLEAN
Test output
18.13.5
Settings
PID-2530-SETTINGS v18
Table 918: GOOSEMVRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
18.13.6
Operation principle
GUID-7B24A6D3-2E5F-4961-A0A6-86436373809E v3
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure condition
and the GOOSE transmission from the sending IED does not happen.
Section 18
1MRK 502 066-UUS B
Station communication
1202
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...