16.4.5
Settings
PID-3267-SETTINGS v9
Table 766: SSCBR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
PhSel
Phase A
Phase B
Phase C
-
-
Phase A
Phase selection
RatedOperCurr
100.00 - 5000.00
A
0.01
1000.00
Rated operating current of the breaker
OperNoRated
1 - 99999
-
1
10000
Number of operations possible at rated
current
RatedFltCurr
500.00 - 99999.99
A
0.01
5000.00
Rated fault current of the breaker
OperNoFault
1 - 10000
-
1
1000
Number of operations possible at rated
fault current
tTrOpenAlm
0.000 - 0.200
s
0.001
0.040
Alarm level for open travel time
tTrCloseAlm
0.000 - 0.200
s
0.001
0.040
Alarm level for close travel time
OperAlmLevel
0 - 9999
-
1
200
Alarm level for number of operations
OperLOLevel
0 - 9999
-
1
300
Lockout level for number of operations
AccSelCal
Aux Contact
Trip Signal
-
-
Trip Signal
Accumulated energy calculation selection
CurrExponent
0.50 - 3.00
-
0.01
2.00
Current exponent value used for energy
calculation
AccStopCurr
5.00 - 100.00
%IB
0.01
10.00
RMS current level below which energy
accumulation stops
AlmAccCurrPwr
0.00 - 20000.00
-
0.01
2500.00
Alarm level for accumulated
I^CurrExponent integrated over CB open
travel time
LOAccCurrPwr
0.00 - 20000.00
-
0.01
2500.00
Lockout level for accumulated
I^CurrExponent integrated over CB open
travel time
SpChAlmTime
0.00 - 60.00
s
0.01
1.00
Alarm level for spring charging time
InitCBRemLife
1 - 99999
-
1
10000
Initial value for remaining life estimates
InactiveAlDays
0 - 9999
Day
1
2000
Alarm level for inactive days counter
Table 767: SSCBR Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
OpenTimeCorr
-0.100 - 0.100
s
0.001
0.010
Correction for open travel time
CloseTimeCorr
-0.100 - 0.100
s
0.001
0.010
Correction for close travel time
DirCoef
-3.00 - -0.50
-
0.01
-1.50
Directional coefficient for CB life
calculation
CBLifeAlmLevel
1 - 99999
-
1
5000
Alarm level for CB remaining life
Table continues on next page
Section 16
1MRK 502 066-UUS B
Monitoring
1050
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...