For Zone 1,
Z
R PEZ
j X PEZ
set
1
1
1
1
1
=
+ ⋅
IECEQUATION15019 V1 EN-US
For Zone 2-5 and RV,
Z
R Zx
j X Zx
set
1
1
1
=
+ ⋅
IECEQUATION15020 V1 EN-US
(Equation 90)
where
Z
set
0
is the complex zero sequence impedance of the line in Ω/phase
Z
set
1
is the complex positive sequence impedance of the line in Ω/
phase
R1PEZ1
is the positive sequence resistive reach of the line in Ω/phase
for phase-to-ground fault for zone 1
X1PEZ1
is the positive sequence reactance reach of the line in Ω/phase
for phase-to-ground fault for zone 1
R0Zx
is the zero sequence resistive reach of the line in Ω/phase for
zone x (x=2-5, or RV)
X0Zx
is the zero sequence reactance reach of the line in Ω/phase for
zone x (x=2-5, or RV)
For an earth fault in phase A, the angle β between the compensation voltage and the polarizing
voltage
V
pol
is,
β =
−
+
⋅
⋅
−
arg [
(
)
]
(
)
V
I
I
K
Z
V
A
A
N
set
pol
3 0
1
arg
ANSIEQUATION15021 V1 EN-US
(Equation 91)
where
V
A
is the phase voltage in faulty phase A
I
A
is the phase current in faulty phase A
3I
0
is the zero-sequence current in faulty phase A
Z
set
1
is the complex positive sequence impedance of the line in Ω/
phase for phase-to-ground fault in zone direction
V
pol
is the polarizing voltage for phase A
Section 7
1MRK 502 066-UUS B
Impedance protection
314
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...