Name
Type
Description
AI2
GROUP SIGNAL
Linear combination of input 2 signals from both SMAI blocks
AI3
GROUP SIGNAL
Linear combination of input 3 signals from both SMAI blocks
AI4
GROUP SIGNAL
Linear combination of input 4 signals from both SMAI blocks
21.10.4
Settings
SEMOD55995-1 v2
SEMOD130361-4 v2
Settings
DFTRefExtOut and DFTReference shall be set to default value
InternalDFTRef if no VT inputs are available.
PID-6428-SETTINGS v3
Table 991: 3PHSUM Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
SummationType
Group2
Group1-Group2
Group2-Group1
-(Group2)
-
-
Group2
Summation type
DFTReference
InternalDFTRef
DFTRefGrp1
External DFT ref
-
-
InternalDFTRef
DFT reference
DFTRefExtOut
InternalDFTRef
DFTRefGrp1
External DFT ref
-
-
InternalDFTRef
DFT reference for external output
Table 992: 3PHSUM Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
FreqMeasMinVal
5 - 200
%
1
10
Amplitude limit for frequency calculation in
% of UBase
21.10.5
Operation principle
SEMOD55749-4 v6
Summation block 3 phase 3PHSUM receives the three-phase signals from Signal matrix for analog
inputs function (SMAI). The BLOCK input will reset all the outputs of the function to 0.
21.11
Global base values GBASVAL
GUID-2FDB0A2C-10FE-4954-B6E4-9DA2EEEF1668 v1
Section 21
1MRK 502 066-UUS B
Basic IED functions
1270
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...