![ABB Relion 670 series Technical Manual Download Page 1159](http://html.mh-extra.com/html/abb/relion-670-series/relion-670-series_technical-manual_30452261159.webp)
18.7.3
Settings
IP14403-1 v2
PID-6195-SETTINGS v4
Table 853: SPA Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SlaveAddress
1 - 899
-
1
30
Slave address
BaudRate
300 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd
-
-
9600 Bd
Baudrate on serial line
PID-6194-SETTINGS v4
Table 854: LONSPA Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation
SlaveAddress
1 - 899
-
1
30
Slave address
18.7.4
Operation principle
IP14401-1 v3
M11880-3 v2
The SPA bus uses an asynchronous serial communications protocol (1 start bit, 7 data bits + even
parity, 1 stop bit) with data transfer rate up to 38400 bit/s. For more information on
recommended baud rate for each type of IED, refer to Technical reference manual. Messages on
the bus consist of ASCII characters.
Introduction of SPA protocol
M11880-7 v2
The basic construction of the protocol assumes that the slave has no self-initiated need to talk to
the master but the master is aware of the data contained in the slaves and, consequently, can
request required data. In addition, the master can send data to the slave. Requesting by the
master can be performed either by sequenced polling (for example, for event information) or only
on demand.
The master requests slave information using request messages and sends information to the
slave in write messages. Furthermore, the master can send all slaves in common a broadcast
message containing time or other data. The inactive state of bus transmit and receive lines is a
logical "1".
SPA protocol
M11880-10 v5
The tables below specify the SPA addresses for reading data from and writing data to an IED with
the SPA communication protocol implemented.
The SPA addresses for the mA input service values (MIM3 to MIM16) are found in table
1MRK 502 066-UUS B
Section 18
Station communication
1153
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...