Table 280: GUPPDUP (37) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
-
-
Pos Seq
Selection of measured current and voltage
8.11.6
Monitored data
PID-3709-MONITOREDDATA v4
Table 281: GUPPDUP (37) Monitored data
Name
Type
Values (Range)
Unit
Description
P
REAL
-
MW
Active Power in MW
PPERCENT
REAL
-
%
Active power in % of SBase
Q
REAL
-
MVAr
Reactive power in MVAr
QPERCENT
REAL
-
%
Reactive power in % of SBase
8.11.7
Operation principle
SEMOD172136-4 v4
A simplified scheme showing the principle of the power protection function is shown in figure
The function has two stages with individual settings.
Chosen current
phasors
Chosen voltage
phasors
Complex
power
calculation
P
Derivation of
S( composant)
in Char angle
S( angle)
S( angle) <
Power1
t
TRIP 1
PICKUP1
Q
P = POWRE
Q = POWIM
S( angle) <
Power2
TRIP2
PICKUP2
0
t
0
ANSI06000438-2-en.vsd
ANSI06000438 V2 EN-US
Figure 290: Simplified logic diagram of the power protection function
Section 8
1MRK 502 066-UUS B
Current protection
546
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...