Two step residual overvoltage protection ROV2PTOV (59N) function calculates the residual voltage
from the three-phase voltage input transformers or measures it from a single voltage input
transformer fed from a broken delta or neutral point voltage transformer.
ROV2PTOV (59N) has two voltage steps, each with inverse or definite time delay.
Reset delay ensures operation for intermittent ground faults.
9.3.3
Function block
M13812-3 v6
ANSI06000278-2-en.vsd
ROV2PTOV (59N)
V3P*
BLOCK
BLKTR1
BLK1
BLKTR2
BLK2
TRIP
TRST1
TRST2
PICKUP
PU_ST1
PU_ST2
ANSI06000278 V2 EN-US
Figure 339: ROV2PTOV (59N) function block
9.3.4
Signals
PID-3531-INPUTSIGNALS v5
Table 347: ROV2PTOV (59N) Input signals
Name
Type
Default
Description
V3P
GROUP
SIGNAL
-
Three phase voltages
BLOCK
BOOLEAN
0
Block of function
BLKTR1
BOOLEAN
0
Block of trip signal, step 1
BLK1
BOOLEAN
0
Block of step 1
BLKTR2
BOOLEAN
0
Block of trip signal, step 2
BLK2
BOOLEAN
0
Block of step 2
PID-3531-OUTPUTSIGNALS v5
Table 348: ROV2PTOV (59N) Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
TRST1
BOOLEAN
Common trip signal from step1
TRST2
BOOLEAN
Common trip signal from step2
PICKUP
BOOLEAN
Common pickup signal
PU_ST1
BOOLEAN
Common pickup signal from step1
PU_ST2
BOOLEAN
Common pickup signal from step2
Section 9
1MRK 502 066-UUS B
Voltage protection
626
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...