comp
V
ß
I
A·
X
I
A
·R
I
A
·ZPE
IA·ZN
loop
A
Z
•
I
f
Vpol
IA (Ref)
en06000472_ansi.vsd
ANSI06000472 V1 EN-US
Figure 103: Simplified offset mho characteristic and vector diagram for phase A-to-ground
fault
Operation occurs if 90≤β≤270.
Offset mho
SEMOD154224-309 v5
The characteristic for offset mho at ground fault is a circle containing the two vectors from the
origin
ZPE and ZRevPE where ZPE and ZrevPE are the setting reach for the positive sequence
impedance in forward respective reverse direction. The vector
ZPE in the impedance plane has the
settable angle
AngZPE and the angle for ZRevPP is 180°.
The condition for operation at phase-to-ground fault is that the angle β between the two
compensated voltages Vcomp1 and Vcomp2 is greater or equal to 90° see figure
. The angle
will be 90° for fault location on the boundary of the circle.
The angle β for A-to-ground fault can be defined as
Table continues on next page
Section 7
1MRK 502 066-UUS B
Impedance protection
228
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...