PID-2450-SETTINGS v8
Table 572: MSTSER Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
ChToAssociate
RS485
Optical
-
-
RS485
Channel to associate to
SlaveAddress
0 - 65519
-
1
1
Slave address
MasterAddres
0 - 65519
-
1
1
Master address
Obj1DefVar
1:BISingleBit
2:BIWithStatus
-
-
1:BISingleBit
Object 1, default variation
Obj2DefVar
1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e
-
-
3:BIChWithRelTi
me
Object 2, default variation
Obj3DefVar
1:DIWithoutFlag
2:DIWithFlag
-
-
1:DIWithoutFlag
Object 3, default variation
Obj4DefVar
1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e
-
-
3:DIChWithRelTi
me
Object 4, default variation
Obj10DefVar
1:BO
2:BOStatus
-
-
2:BOStatus
Object 10, default variation
Obj20DefVar
1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
-
-
5:BinCnt32WoutF
Object 20, default variation
Obj22DefVar
1:BinCnt32EvWout
T
2:BinCnt16EvWou
tT
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
-
-
1:BinCnt32EvWou
tT
Object 22, default variation
Obj30DefVar
1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
-
-
3:AI32IntWithout
F
Object 30, default variation
Obj32DefVar
1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithF
T
-
-
1:AI32IntEvWoutF
Object 32, default variation
Section 14
1MRK 502 066-UUS B
Control
922
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...