16.7
Logical signal status report BINSTATREP
GUID-E7A2DB38-DD96-4296-B3D5-EB7FBE77CE07 v2
16.7.1
Identification
GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logical signal status report
BINSTATREP
-
-
16.7.2
Functionality
GUID-A72E490D-01F7-4874-B010-8BDE38391D88 v3
The Logical signal status report (BINSTATREP) function makes it possible for a SPA master to poll
signals from various other functions.
16.7.3
Function block
GUID-BA0A5BC3-493B-4FE3-B4A9-14F60A88A22F v2
BINSTATREP
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
OUTPUT9
OUTPUT10
OUTPUT11
OUTPUT12
OUTPUT13
OUTPUT14
OUTPUT15
OUTPUT16
IEC09000730-1-en.vsd
IEC09000730 V1 EN-US
Figure 565: BINSTATREP function block
16.7.4
Signals
PID-4144-INPUTSIGNALS v4
Table 783: BINSTATREP Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
INPUT1
BOOLEAN
0
Single status report input 1
INPUT2
BOOLEAN
0
Single status report input 2
INPUT3
BOOLEAN
0
Single status report input 3
INPUT4
BOOLEAN
0
Single status report input 4
Table continues on next page
1MRK 502 066-UUS B
Section 16
Monitoring
1089
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...