Time Integration
Transgression Supervision
Plus Retain
BLOCK
ACCTIME
RESET
IN
tAlarm
OVERFLOW
WARNING
ALARM
IEC12000195-3-en.vsd
Loop Delay
Loop Delay
tWarning
IEC12000195 V3 EN-US
Figure 525: TEIGAPC Simplified logic
TEIGAPC main functionalities
•
integration of the elapsed time when IN has been high
•
applicable to long time integration (≤999 999.9 seconds)
•
output
ACCTIME
presents integrated value in seconds
•
integrated value is retained in nonvolatile memory
•
any retained value with a warning/alarm/overflow is used as initiation value for the
integration following by a restart
•
RESET
: Reset of the integration value. Consequently all other outputs are also reset
•
unconditionally on the input
IN
value
•
reset the value of the nonvolatile memory to zero
•
BLOCK
: Freeze the integration and block/reset the other outputs
•
unconditionally on the signal value
•
BLOCK
request overrides
RESET
request
•
Monitor and report the conditions of limit transgression
•
overflow if output
ACCTIME
>999999.9 seconds
•
alarm if
ACCTIME
>
tAlarm
•
warning if
ACCTIME
>
tWarning
The
ACCTIME
output represents the integrated time in seconds while
tOverflow, tAlarm and
tWarning are the time limit parameters in seconds.
tAlarm and tWarning are user settable limits. They are also independent, that is, there is no check
if
tAlarm > tWarning.
tAlarm and tWarning are possible to be defined with a resolution of 10 ms, depending on the level
of the defined values for the parameters.
The limit for the overflow supervision is fixed at 999999.9 seconds. The outputs freeze if an
overflow occurs.
1MRK 502 066-UUS B
Section 15
Logic
1001
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...