PID-3924-SETTINGS v5
Table 19: TRM_9I_3U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CT_WyePoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
1 - 10
A
1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
1 - 10
A
1
1
Rated CT secondary current
CTprim2
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
1 - 10
A
1
1
Rated CT secondary current
CTprim3
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
1 - 10
A
1
1
Rated CT secondary current
CTprim4
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint5
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec5
1 - 10
A
1
1
Rated CT secondary current
CTprim5
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint6
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec6
1 - 10
A
1
1
Rated CT secondary current
CTprim6
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint7
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec7
1 - 10
A
1
1
Rated CT secondary current
CTprim7
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint8
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec8
1 - 10
A
1
1
Rated CT secondary current
CTprim8
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint9
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec9
1 - 10
A
1
1
Rated CT secondary current
CTprim9
1 - 99999
A
1
3000
Rated CT primary current
VTsec10
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim10
0.05 - 2000.00
kV
0.05
400.00
Rated VT primary voltage
VTsec11
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
Table continues on next page
1MRK 502 066-UUS B
Section 3
Analog inputs
75
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...