AND
a
b
b>a
Selected voltage
PickupVolt_UV1
Operation_UV1=On
BLKUV1
Inverse time
selected
en05000752_ansi.vsd
Inverse
0-DEF
DEF time
selected
OR
PU_UV1
TRUV1
AND
BLKTRUV1
0
ANSI05000752 V1 EN-US
Figure 382: Simplified internal logic diagram for built-in first undervoltage step UV1 (step UV2 has the same
internal logic)
11.1.8
Technical data
M13095-2 v7
Table 414: CVGAPC technical data
Function
Range or value
Accuracy
Measuring current input
Phase A, Phase B, Phase C, PosSeq, -
NegSeq, -3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, Phase A-Phase B, Phase
B-Phase C, Phase C-Phase A, MaxPh-
Ph, MinPh-Ph, UnbalancePh-Ph
-
Measuring voltage input
Phase A, Phase B, Phase C, PosSeq, -
NegSeq, -3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, Phase A-Phase B, Phase
B-Phase C, Phase C-Phase A, MaxPh-
Ph, MinPh-Ph, UnbalancePh-Ph
-
Pickup overcurrent, step 1 - 2
(2 - 5000)% of IBase
±1.0% of I
n
at I ≤ I
n
±1.0% of I at I > I
n
Pickup undercurrent, step 1-2
(2 - 150)% of IBase
±1.0% of I
n
at I ≤ I
n
±1.0% of I at I > I
n
Independent time delay, overcurrent at
0 to 2 x I
set
, step 1 - 2
(0.00 - 6000.00) s
±0.2% or ±35 ms whichever is
greater
Independent time delay, undercurrent
at 2 to 0 x I
set
, step 1 - 2
(0.00 - 6000.00) s
±0.2% or ±35 ms whichever is
greater
Overcurrent (non-directional):
Pickup time at 0 to 2 x I
set
Min. = 15 ms
Max. = 30 ms
-
Reset time at 2 to 0 x I
set
Min. = 15 ms
Max. = 30 ms
-
Pickup time at 0 to 10 x I
set
Min. = 5 ms
Max. = 20 ms
-
Table continues on next page
Section 11
1MRK 502 066-UUS B
Multipurpose protection
712
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...