2
Vm Vn
ZPHS
In
-
=
- ×
EQUATION1813-ANSI V1 EN-US
(Equation 50)
Vm is the leading phase voltage, Vn the lagging phase voltage and In the phase current in the
lagging phase n.
The operation characteristic is shown in figure
.
ANSI05000670-2-en.vsd
X1
R
X
0.5·
RFltFwdPP
Kr·X1
Kr·X1
X1
60 deg
60 deg
0.5·
RFltFwdPP
0.5·
RFltRevPP
0.5·
RFltRevPP
0.5·
RFltRevPP
1
Kr
tan(60 deg)
=
0.5·
RFltFwdPP
)
/
(
phase
W
)
/
(
phase
W
ANSI05000670 V2 EN-US
Figure 84: The operation characteristics for FDPSPDIS (21) at phase-to-phase fault (setting
parameters in italic, directional lines drawn as "line-dot-dot-line"), ohm/phase
domain
In the same way as the condition for phase-to-ground fault, there are current conditions that have
to be fulfilled in order to release the phase-to-phase loop. Those are according to equation
equation
0
3
I
IMinPUPG
<
EQUATION2109-ANSI V1 EN-US
(Equation 51)
Section 7
1MRK 502 066-UUS B
Impedance protection
204
Technical manual