The sum of the value on each INx corresponds to the integer presented on the output OUT on the
function block B16I
Name of input
Type
Default
Description
Value when
activated
Value when
deactivated
IN1
BOOLEAN
0
Input 1
1
0
IN2
BOOLEAN
0
Input 2
2
0
IN3
BOOLEAN
0
Input 3
4
0
IN4
BOOLEAN
0
Input 4
8
0
IN5
BOOLEAN
0
Input 5
16
0
IN6
BOOLEAN
0
Input 6
32
0
IN7
BOOLEAN
0
Input 7
64
0
IN8
BOOLEAN
0
Input 8
128
0
IN9
BOOLEAN
0
Input 9
256
0
IN10
BOOLEAN
0
Input 10
512
0
IN11
BOOLEAN
0
Input 11
1024
0
IN12
BOOLEAN
0
Input 12
2048
0
IN13
BOOLEAN
0
Input 13
4096
0
IN14
BOOLEAN
0
Input 14
8192
0
IN15
BOOLEAN
0
Input 15
16384
0
IN16
BOOLEAN
0
Input 16
32768
0
The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16) are active
that is=1; is 65535. 65535 is the highest boolean value that can be converted to an integer by the
B16I function block.
15.10.7
Technical data
GUID-65A2876A-F779-41C4-ACD7-7662D1E7F1F2 v1
Table 690: Number of B16I instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
B16I
6
4
8
15.11
Boolean to integer conversion with logical node
representation, 16 bit BTIGAPC
SEMOD175753-1 v4
Section 15
1MRK 502 066-UUS B
Logic
986
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...