Name
Type
Description
ICOSFI
REAL
Measured current multiplied with cos (Phi)
VOLTAGE
REAL
Measured voltage value
VIANGLE
REAL
Angle between voltage and current
11.1.5
Settings
PID-3857-SETTINGS v7
Table 405: CVGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
CurrentInput
Phase A
Phase B
Phase C
PosSeq
NegSeq
3*ZeroSeq
MaxPh
MinPh
UnbalancePh
Phase AB
Phase BC
Phase CA
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
-
-
MaxPh
Select current signal which will be
measured inside function
VoltageInput
Phase A
Phase B
Phase C
PosSeq
-NegSeq
-3*ZeroSeq
MaxPh
MinPh
UnbalancePh
Phase AB
Phase BC
Phase CA
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
-
-
MaxPh
Select voltage signal which will be
measured inside function
OperHarmRestr
Disabled
Enabled
-
-
Disabled
Disable/Enable operation of 2nd harmonic
restrain
l_2nd/l_fund
10.0 - 50.0
%
1.0
20.0
Ratio of second to fundamental current
harmonic in %
BlkLevel2nd
10 - 5000
%IB
1
5000
Harm analyse disabled above this current
level in % of fundamental current
EnRestrainCurr
Disabled
Enabled
-
-
Disabled
Disable/Enable current restrain function
RestrCurrInput
PosSeq
NegSeq
3*ZeroSeq
Max
-
-
PosSeq
Select current signal which will be used for
current restrain
Table continues on next page
Section 11
1MRK 502 066-UUS B
Multipurpose protection
690
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...