PID-3649-OUTPUTSIGNALS v5
Table 122: ZMRPDIS (21) Output signals
Name
Type
Description
TRIP
BOOLEAN
General Trip, issued from any phase or loop
TR_A
BOOLEAN
Trip signal from phase A
TR_B
BOOLEAN
Trip signal from phase B
TR_C
BOOLEAN
Trip signal from phase C
RI
BOOLEAN
General Pickup, issued from any phase or loop
BFI_A
BOOLEAN
Pickup signal from phase A
BFI_B
BOOLEAN
Pickup signal from phase B
PU_C
BOOLEAN
Pickup signal from phase C
PHPUND
BOOLEAN
Non-directional pickup, issued from any selected phase or loop
PID-3648-INPUTSIGNALS v5
Table 123: ZMRAPDIS (21) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group signal for current input
V3P
GROUP
SIGNAL
-
Group signal for voltage input
BLOCK
BOOLEAN
0
Block of function
BLKZ
BOOLEAN
0
Blocks all output for LOV (or fuse failure) condition
BLKTR
BOOLEAN
0
Blocks all trip outputs
PHSEL
INTEGER
0
Faulted phase loop selection enable from phase selector
DIRCND
INTEGER
0
External directional condition
PID-3648-OUTPUTSIGNALS v5
Table 124: ZMRAPDIS (21) Output signals
Name
Type
Description
TRIP
BOOLEAN
General Trip, issued from any phase or loop
TR_A
BOOLEAN
Trip signal from phase A
TR_B
BOOLEAN
Trip signal from phase B
TR_C
BOOLEAN
Trip signal from phase C
BFI
BOOLEAN
General Pickup, issued from any phase or loop
PU_A
BOOLEAN
Pickup signal from phase A
BFI_B
BOOLEAN
Pickup signal from phase B
PU_C
BOOLEAN
Pickup signal from phase C
PHPUND
BOOLEAN
Non-directional pickup, issued from any selected phase or loop
Section 7
1MRK 502 066-UUS B
Impedance protection
256
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...