Table 1037:The arrangement for the pins
Pin
Name 2-wire
Name 4-wire
Description
1
RS485+
TX+
Receive/transmit high or transmit high
2
RS485–
TX–
Receive/transmit
3
Term
T-Term
Termination resistor for transmitter (and receiver in 2–wir case)
(connect to TX+)
4
N.A.
R-Term
Termination resistor for receiver (connect to RX+)
5
N.A.
RX–
Receive low
6
N.A.
RX+
Receive high
Screw
terminal
X3
1
2
1
2
3
4
5
6
Screw
terminal
X1
Backplane
Angle
bracket
RS485
PWB
IEC06000517 V1 EN-US
Figure 661: RS485 connector
•
2-wire: Connect pin 1 to pin 6 and pin 2 to pin 5
•
Termination (2-wire): Connect pin 1 to pin 3
•
Termination (4-wire): Connect pin 1 to pin 3 and pin 4 to pin 6
Soft ground connector pinouts
SEMOD158670-45 v1
A second 2-pole screw connector is used for the connection of IO-ground. It can be used in two
combinations like:
•
Unconnected: No ground of the IO-part · .
•
Soft grounded: The IO is connected to the GND with an RC net parallel with a MOV
Section 22
1MRK 502 066-UUS B
IED hardware
1322
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...