REG 670
RXTTE 4
I
V
230 V AC
120 V AC
0
Generator rotor winding
G
313
314
315
421
428
324
325
221
222
Optional external
resistor
Connection to be done by
the panel builder / field
contractor
en07000185_ansi.vsd
321
ANSI07000185 V1 EN-US
Figure 383: Connection of rotor ground fault protection
By using a two stage directional current measurement in the General current and voltage
protection (CVGAPC), as shown in figure
, the ground fault current on the DC side of the
excitation is detected. The protection operates when the resistive component of the measured
injected current exceeds the pre-set operate level. Stage one provides an alarm signal and stage
two trips the generator after a short time delay for fully developed rotor ground faults.
Section 11
1MRK 502 066-UUS B
Multipurpose protection
716
Technical manual