PID-6500-OUTPUTSIGNALS v3
Table 489: SCSWI Output signals
Name
Type
Description
EXE_OP
BOOLEAN
Execute Open command
EXE_CL
BOOLEAN
Execute Close command
SEL_OP
BOOLEAN
Selected for open command
SEL_CL
BOOLEAN
Selected for close command
SELECTED
BOOLEAN
Select conditions are fulfilled
RES_RQ
BOOLEAN
Request signal to the reservation function
START_SY
BOOLEAN
Starts the external synchronizing function
CANC_SY
BOOLEAN
Cancels the external synchronizing function, started through
START_SY
POSITION
INTEGER
Position indication
OPENPOS
BOOLEAN
Open position indication
CLOSEPOS
BOOLEAN
Closed position indication
POLEDISC
BOOLEAN
The positions for poles A, B and C are not equal after a set time
CMD_BLK
BOOLEAN
Commands are blocked
L_CAUSE
INTEGER
Latest value of the error indication during command
POS_INTR
BOOLEAN
Stopped in intermediate position
XOUT
BOOLEAN
Execution information to XCBR/XSWI
GUID-7DABB496-EABE-48A4-8078-7ED5D6D4FE14 v2
AU_OPEN and AU_CLOSE are used to issue automated commands as e.g. for load
shedding for opening respectively closing to the SCSWI function. They work
without regard to how the operator place selector, PSTO, is set. In order to have
effect on the outputs EXE_OP and EXE_CL, the corresponding enable input,
EN_OPEN respectively EN_CLOSE must be set, and that no interlocking is active.
L_SEL, L_OPEN and L_CLOSE are used for local command sequence connected to
binary inputs. In order to have effect, the operator place selector, PSTO, must be
set to local or to remote with no priority. If the control model used is Select before
operate, Also the corresponding enable input must be set, and no interlocking is
active. The L_SEL input must be set before L_OPEN or L_CLOSE is operated, if the
control model is Select before operate.
If one multi-phase XCBR/XSWI or two single-phase XCBR/XSWI are used for a two-
or three-phase system, two or more of the inputs XPOSL1, XPOSL2 and XPOSL3 are
connected to the same source.
Section 14
1MRK 502 066-UUS B
Control
838
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...