A
loop
pol
Vcomp
V
I
Z
=
-
×
EQUATION1793-ANSI V1 EN-US
(Equation 57)
where
V
pol
is the polarizing voltage (memorized VA for Phase A-to- ground
fault)
Z
loop
is the loop impedance, which in general terms can be expressed
as
(
)
1
1
Z +ZN
1
Z
KN
=
× +
where
Z
1
is the positive sequence impedance of the line (Ohm/phase)
KN
is the zero-sequence compensator factor
The angle β between the Vcomp and the polarize voltage Vpol for a A-to-ground fault is
(
)
A
A
arg V
I
IN KN ZPE
arg(Vpol)
b =
-
+
×
×
-
é
ù
ë
û
EQUATION1592 V1 EN-US
(Equation 58)
where
V
A
is the phase voltage in faulty phase A
I
A
is the phase current in faulty phase A
IN
is the zero-sequence current in faulty phase A (3I0)
KN
Z0-Z1
3 Z1
×
the setting parameter for the zero sequence compensation
consisting of the magnitude
KN and the angle KNAng.
V
pol
is the 100% of positive sequence memorized voltage V
A
1MRK 502 066-UUS B
Section 7
Impedance protection
227
Technical manual