![ABB Relion 670 series Technical Manual Download Page 354](http://html.mh-extra.com/html/abb/relion-670-series/relion-670-series_technical-manual_3045226354.webp)
VA
R1 + j X1
IA
RFPG
Phase-to-ground
fault in phase A
Phase-to-phase
fault in phase
A-B
Three-phase
fault or Phase-to-
phase-ground fault
(Arc + tower
resistance)
N
(R0-R1)/3 +
j (X0-X1)/3 )
IG
VA
R1 + j X1
IA
VB
R1 + j X1
IB
RFPP
VA
R1 + j X1
IA
VC
R1 + j X1
IC
0.5·RFPP
0.5·RFPP
(Arc resistance)
Phase-to-ground
element
Phase-to-phase
element A-B
Phase-to-phase
element A-C
ANSI11000419-3-en.vsd
ANSI11000419 V3 EN-US
Figure 175: Fault loop model
Mho characteristic
GUID-DA87F1BC-8037-4E14-96E0-03BCD98ED6F2 v1
ZMFCPDIS implements quadrilateral and mho characteristic in all the six zones separately. Set
OpModePEZx or OpModePPZx setting to Mho or Offset, to choose a particular measuring loop in a
zone to work as mho (or Offset Mho) distance protection.
Zones 3 to 5 can be selected to be either forward or reverse with positive sequence polarized mho
characteristic; alternatively self polarized offset mho characteristics. The operating characteristic
where zone 5 is selected offset mho.
Section 7
1MRK 502 066-UUS B
Impedance protection
348
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...