PID-4047-OUTPUTSIGNALS v5
Table 708: TEIGAPC Output signals
Name
Type
Description
WARNING
BOOLEAN
Indicator of the integrated time has reached the warning limit
ALARM
BOOLEAN
Indicator of the integrated time has reached the alarm limit
OVERFLOW
BOOLEAN
Indicator of the integrated time has reached the overflow limit
ACCTIME
REAL
Integrated elapsed time in seconds
15.15.5
Settings
PID-4047-SETTINGS v5
Table 709: TEIGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
tWarning
1.00 - 999999.99
s
0.01
600.00
Time limit for warning supervision
tAlarm
1.00 - 999999.99
s
0.01
1200.00
Time limit for alarm supervision
15.15.6
Operation principle
GUID-04CC8365-DCDE-4DC7-BEF0-6EF8382305DD v3
The elapsed time integrator (TEIGAPC) provides
•
time integration, accumulating the elapsed time when a given binary signal has been high
•
blocking and reset of the total integrated time
•
supervision of limit transgression and overflow, the overflow limit is fixed to 999999.9
seconds
•
retaining of the integrated value
Figure
describes the simplified logic of the function where the block “Time Integration“ covers
the logics for the first two items listed above while the block “Transgression Supervision Plus
Retain“ contains the logics for the last two.
Section 15
1MRK 502 066-UUS B
Logic
1000
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...