Name
Type
Default
Description
I3PDIR
GROUP
SIGNAL
-
Group connection for directional current
BLOCK
BOOLEAN
0
General block
BLKTR
BOOLEAN
0
Block of trip
BLK1
BOOLEAN
0
Block of step 1 (Pickup and trip)
BLK2
BOOLEAN
0
Block of step 2 (Pickup and trip)
BLK3
BOOLEAN
0
Block of step 3 (Pickup and trip)
BLK4
BOOLEAN
0
Block of step 4 (Pickup and trip)
MULTPU1
BOOLEAN
0
When activated, the pickup multiplier is in use for step1
MULTPU2
BOOLEAN
0
When activated, the pickup multiplier is in use for step2
MULTPU3
BOOLEAN
0
When activated, the pickup multiplier is in use for step3
MULTPU4
BOOLEAN
0
When activated, the pickup multiplier is in use for step4
52a
BOOLEAN
0
Breaker position
CLOSECMD
BOOLEAN
0
Breaker close command
OPENCMD
BOOLEAN
0
Breaker open command
PID-6529-OUTPUTSIGNALS v4
Table 228: EF4PTOC (51N_67N) Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip signal
TRST1
BOOLEAN
Trip signal from step 1
TRST2
BOOLEAN
Trip signal from step 2
TRST3
BOOLEAN
Trip signal from step 3
TRST4
BOOLEAN
Trip signal from step 4
TRSOTF
BOOLEAN
Trip signal from switch onto fault function
PICKUP
BOOLEAN
Common pickup signal
PUST1
BOOLEAN
Pickup signal step 1
PUST2
BOOLEAN
Pickup signal step 2
PUST3
BOOLEAN
Pickup signal step 3
PUST4
BOOLEAN
Pickup signal step 4
PUSOTF
BOOLEAN
Pickup signal from switch onto fault function
PUFW
BOOLEAN
Pick up foward direction
PUREV
BOOLEAN
Pick up reverse direction
2NDHARMD
BOOLEAN
2nd harmonic block signal
8.4.5
Settings
IP11454-1 v2
Section 8
1MRK 502 066-UUS B
Current protection
472
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...