PID-3966-SETTINGS v5
Table 960: TIMESYNCHGEN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CoarseSyncSrc
Disabled
SPA
LON
SNTP
DNP
IEC103
-
-
Disabled
Coarse time synchronization source
FineSyncSource
Disabled
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
-
-
Disabled
Fine time synchronization source
SyncMaster
Disabled
SNTP-Server
-
-
Disabled
Activate IEDas synchronization master
TimeAdjustRate
Slow
Fast
-
-
Fast
Adjust rate for time synchronization
HWSyncSrc
Disabled
GPS
IRIG-B
PPS
-
-
Disabled
Hardware time synchronization source
AppSynch
NoSynch
Synch
-
-
NoSynch
Time synchronization mode for application
SyncAccLevel
Class T5 (1us)
Class T4 (4us)
Unspecified
-
-
Unspecified
Wanted time synchronization accuracy
PID-6188-SETTINGS v4
Table 961: BININPUT Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
ModulePosition
3 - 16
-
1
3
Hardware position of IO module for time
synchronization
BinaryInput
1 - 16
-
1
1
Binary input number for time
synchronization
BinDetection
PositiveEdge
NegativeEdge
-
-
PositiveEdge
Positive or negative edge detection
Section 21
1MRK 502 066-UUS B
Basic IED functions
1238
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...