The type C curve is described as:
t
TD
V
Vpickup
Vpickup
=
⋅
⋅
−
>
>
−
+
480
32
0 5
0 035
.
.
ANSIEQUATION2288 V2 EN-US
(Equation 178)
The customer programmable curve is defined by the below equation, where A, B, C, D, k and p are
settings:
P
TD A
t
D
V Vpickup
B
C
Vpickup
×
=
+
-
×
-
æ
ö
ç
÷
è
ø
EQUATION1616 V1 EN-US
(Equation 179)
When the denominator in the expression is equal to zero the time delay will be infinity. There will
be an undesired discontinuity. Therefore, a tuning parameter
CrvSatn is set to compensate for this
phenomenon. In the voltage interval Vpickup up to Vpickup · (1.0 +
CrvSatn/100) the used voltage
will be: Vpickup · (1.0 +
CrvSatn/100). If the programmable curve is used this parameter must be
calculated so that:
0
100
CrvSatn
B
C
×
- >
EQUATION1435 V1 EN-US
(Equation 180)
The highest phase (or phase-to-phase) voltage is always used for the inverse time delay
. The details of the different inverse time characteristics are shown in
Section 9
1MRK 502 066-UUS B
Voltage protection
618
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...