18.8.11.3
Function block
GUID-52D27CDA-8805-48FA-99BE-2E05A438B0C7 v1
IEC10000283-1-en.vsd
I103IEDCMD
BLOCK
19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
IEC10000283 V1 EN-US
Figure 603: I103IEDCMD function block
18.8.11.4
Signals
PID-3788-INPUTSIGNALS v4
Table 879: I103IEDCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of commands
PID-3788-OUTPUTSIGNALS v4
Table 880: I103IEDCMD Output signals
Name
Type
Description
19-LEDRS
BOOLEAN
Information number 19, reset LEDs
23-GRP1
BOOLEAN
Information number 23, activate setting group 1
24-GRP2
BOOLEAN
Information number 24, activate setting group 2
25-GRP3
BOOLEAN
Information number 25, activate setting group 3
26-GRP4
BOOLEAN
Information number 26, activate setting group 4
18.8.11.5
Settings
PID-3788-SETTINGS v4
Table 881: I103IEDCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
255
Function type (1-255)
18.8.12
Function commands user defined for IEC 60870-5-103
I103USRCMD
18.8.12.1
Functionality
GUID-2989EAC8-20BE-46EE-93FE-C70188D0BC89 v1
I103USRCMD is a command block in control direction with user defined output signals. These
function blocks include the
FunctionType parameter for each block in the private range, and the
Information number parameter for each output signal.
Section 18
1MRK 502 066-UUS B
Station communication
1176
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...