Name
Values (Range)
Unit
Step
Default
Description
I1Min
0.0 - 500.0
%IB
0.1
50.0
Minimum value in % of IBase
I1Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
I1RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
I1AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
I1AngMax
-180.000 -
180.000
Deg
0.001
180.000
Maximum value
I1AngRepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
I2DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
I2ZeroDb
0 - 100000
m%
1
1
Zero point clamping
I2Min
0.0 - 500.0
%IB
0.1
50.0
Minimum value in % of IBase
I2Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
I2RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
I2LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
I2AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
I2AngMin
-180.000 -
180.000
Deg
0.001
-180.000
Minimum value
I2AngRepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
Table 739: CMSQI Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
3I0HiHiLim
0.0 - 500.0
%IB
0.1
150.0
High High limit in % of IBase
3I0HiLim
0.0 - 500.0
%IB
0.1
120.0
High limit in % of IBase
3I0LowLim
0.0 - 500.0
%IB
0.1
80.0
Low limit in % of IBase
3I0LowLowLim
0.0 - 500.0
%IB
0.1
60.0
Low Low limit in % of IBase
3I0AngZeroDb
0 - 100000
m%
1
0
Zero point clamping in 0.001% of range
I1HiHiLim
0.0 - 500.0
%IB
0.1
150.0
High High limit in % of IBase
I1HiLim
0.0 - 500.0
%IB
0.1
120.0
High limit in % of IBase
I1LowLim
0.0 - 500.0
%IB
0.1
80.0
Low limit in % of IBase
I1LowLowLim
0.0 - 500.0
%IB
0.1
60.0
Low Low limit in % of IBase
I1LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
I1AngZeroDb
0 - 100000
m%
1
0
Zero point clamping in 0.001% of range
Table continues on next page
1MRK 502 066-UUS B
Section 16
Monitoring
1023
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...