7.11.6
Monitored data
PID-3539-MONITOREDDATA v7
Table 169: OOSPPAM (78) Monitored data
Name
Type
Values (Range)
Unit
Description
CURRENT
REAL
-
A
Magnitude of the measured positive-
sequence current, in A
VOLTAGE
REAL
-
kV
Magnitude of the measured positive-
sequence voltage, in V
R
REAL
-
%
Real part of measured positive-sequence
impedance % of VBase/(sqrt(3)*IBase)
X
REAL
-
%
Imaginary part of measured positive-seq
impedance % of VBase/(sqrt(3)*IBase)
SLIPFREQ
REAL
-
Hz
Slip frequency in Hz
ROTORANG
REAL
-
deg
Rotor angle as estimated by the out-of-
step function
VCOSPHI
REAL
-
kV
Estimated Ucos(Phi) voltage during pole
slip, in V
7.11.7
Operation principle
GUID-787EEB01-B760-4D4B-AB4E-1DCD6ABFFF5E v6
General
Under balanced and stable conditions, a generator operates with a constant rotor angle (power
angle), delivering active electrical power to the power system, which is approximately equal to the
input mechanical power on the generator axis.The currents and voltages are constant and stable.
An out-of-step condition is characterized by periodic changes in the rotor angle, that leads to a
wild flow of the synchronizing power; so there are also periodic changes of rotational speed,
currents and voltages. When displayed in the complex impedance plane, these changes are
characterized by a cyclic change in the complex load impedance Z(R, X) as measured at the
terminals of the generator, or at the location of the instrument transformers of a power line
connecting two power subsystems. This is shown in
Section 7
1MRK 502 066-UUS B
Impedance protection
378
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...