Name
Values (Range)
Unit
Step
Default
Description
IMinPUPP
10 - 1000
%IB
1
20
Minimum operate delta current for Phase-
Phase loops
IMinPUPG
10 - 1000
%IB
1
20
Minimum pickup phase current for Phase-
to-ground loops
IMinOpIR
5 - 1000
%IB
1
5
Minimum operate residual current for
Phase-Ground loops
Table 128: ZMRPDIS (21) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
PID-3648-SETTINGS v5
Table 129: ZMRAPDIS (21) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
OperationDir
Non-directional
Forward
Reverse
-
-
Forward
Operation mode of directionality NonDir /
Forw / Rev
X1PP
0.10 - 3000.00
Ohm/p
0.01
30.00
Positive sequence reactance reach Ph-Ph
R1PP
0.01 - 1000.00
Ohm/p
0.01
5.00
Positive seq. resistance for characteristic
angle, Ph-Ph
X1PG
0.10 - 3000.00
Ohm/p
0.01
30.00
Positive sequence reactance reach Ph-G
R1PG
0.01 - 1000.00
Ohm/p
0.01
5.00
Positive seq. resistance for characteristic
angle, Ph-G
RFPP
0.10 - 3000.00
Ohm/l
0.01
30.00
Fault resistance reach in ohm/loop, Ph-Ph
X0PG
0.10 - 9000.00
Ohm/p
0.01
100.00
Zero sequence reactance reach, Ph-G
RFPG
0.10 - 9000.00
Ohm/l
0.01
100.00
Fault resistance reach in ohm/loop, Ph-G
R0PG
0.01 - 3000.00
Ohm/p
0.01
15.00
Zero seq. resistance for zone
characteristic angle, Ph-G
OperationPP
Disabled
Enabled
-
-
Enabled
Operation mode Disable/Enable of Phase-
Phase loops
OpModetPP
Disabled
Enabled
-
-
Enabled
Operation mode Disable/Enable of Zone
timer, Ph-Ph
tPP
0.000 - 60.000
s
0.001
0.000
Time delay of trip, Ph-Ph
OperationPG
Disabled
Enabled
-
-
Enabled
Operation mode Disable/Enable of Phase-
Ground loops
OpModetPG
Disabled
Enabled
-
-
Enabled
Operation mode Disable/ Enable of Zone
timer, Ph-G
tPG
0.000 - 60.000
s
0.001
0.000
Time delay of trip, Ph-G
IMinPUPP
10 - 1000
%IB
1
20
Minimum operate delta current for Phase-
Phase loops
IMinPUPG
10 - 1000
%IB
1
20
Minimum pickup phase current for Phase-
to-ground loops
Section 7
1MRK 502 066-UUS B
Impedance protection
258
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...