9.2.8
Technical data
IP13013-1 v1
M13304-1 v12
Table 346: OV2PTOV (59) technical data
Function
Range or value
Accuracy
Trip voltage, step 1 and 2
(1.0-200.0)% of
VBase
±0.5% of V
n
at V ≤ V
n
±0.5% of V at V > V
n
Absolute hysteresis
(0.0–50.0)% of
VBase
±0.5% of V
n
at V ≤ V
n
±0.5% of V at V > V
n
Inverse time characteristics for
steps 1 and 2, see table
-
See table
Definite time delay, low step (step
1) at 0 to 1.2 x V
set
(0.00 - 6000.00) s
±0.2% or ±45 ms whichever is
greater
Definite time delay, high step
(step 2) at 0 to 1.2 x V
set
(0.000-60.000) s
±0.2% or ±45 ms whichever is
greater
Minimum trip time, Inverse
characteristics
(0.000-60.000) s
±0.2% or ±45 ms whichever is
greater
Trip time, pickup at 0 to 2 x V
set
Min. = 15 ms
Max. = 30 ms
-
Reset time, pickup at 2 to 0 x V
set
Min. = 15 ms
Max. = 30 ms
-
Trip time, pickup at 0 to 1.2 x V
set
Min. = 20 ms
Max. = 35 ms
-
Reset time, , pickup at 1.2 to 0 x
V
set
Min. = 5 ms
Max. = 25 ms
-
Critical impulse time
10 ms typically at 0 to 2 x V
set
-
Impulse margin time
15 ms typically
-
9.3
Two step residual overvoltage protection ROV2PTOV
(59N)
IP14546-1 v4
9.3.1
Identification
SEMOD54295-2 v5
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Two step residual overvoltage
protection
ROV2PTOV
3U0
TRV V1 EN-US
59N
9.3.2
Functionality
M13808-3 v10
Residual voltages may occur in the power system during ground faults.
1MRK 502 066-UUS B
Section 9
Voltage protection
625
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...