18.4.7.1
Functionality
GUID-A90FDBA7-D4D7-4CBD-9F05-13DCC9971779 v5
Redundant station bus communication according to IEC 62439-3 Edition 1 and IEC 62439-3 Edition
2 parallel redundancy protocol (PRP) are available as options when ordering IEDs. Redundant
station bus communication according to IEC 62439-3 uses both port AB and port CD on the OEM
module.
18.4.7.2
Function block
GUID-876EDB9C-BEF1-4DBE-967D-5BEEEA6AFF38 v3
PRPSTATUS
PRP-A LINK
PRP-A VALID
PRP-B LINK
PRP-B VALID
IEC09000757.vsd
IEC09000757 V2 EN-US
Figure 586: PRPSTATUS function block
18.4.7.3
Signals
PID-4074-OUTPUTSIGNALS v4
Table 820: PRPSTATUS Output signals
Name
Type
Description
PRP-A LINK
BOOLEAN
PRP-A Link Status
PRP-A VALID
BOOLEAN
PRP-A Link Valid
PRP-B LINK
BOOLEAN
PRP-B Link Status
PRP-B VALID
BOOLEAN
PRP-B Link Valid
18.4.7.4
Settings
PID-3190-SETTINGS v5
Table 821: PRP Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
PRPMode
PRP-0
PRP-1
-
-
PRP-1
PRP Mode
IPAddress
0 - 18
IP
Address
1
192.168.7.10
IP-Address
IPMask
0 - 18
IP
Address
1
255.255.255.0
IP-Mask
1MRK 502 066-UUS B
Section 18
Station communication
1121
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...