16.9.6
Settings
PID-3553-SETTINGS v5
Table 791: L4UFCNT Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
On
-
-
Disabled
Operation Disabled/Enabled
CountType
Positive edge
Negative edge
Both edges
-
-
Positive edge
Select counting on positive and/or
negative sides
CounterLimit1
1 - 65535
-
1
100
Value of the first limit
CounterLimit2
1 - 65535
-
1
200
Value of the second limit
CounterLimit3
1 - 65535
-
1
300
Value of the third limit
CounterLimit4
1 - 65535
-
1
400
Value of the fourth limit
MaxValue
1 - 65535
-
1
500
Maximum count value
OnMaxValue
Stop
Rollover Steady
Rollover Pulsed
-
-
Stop
Select if counter stops or rolls over after
reaching maxValue with steady or pulsed
overflow flag
InitialValue
0 - 65535
-
1
0
Initial count value after reset of the
function
16.9.7
Monitored data
PID-3553-MONITOREDDATA v4
Table 792: L4UFCNT Monitored data
Name
Type
Values (Range)
Unit
Description
VALUE
INTEGER
-
-
Counted value
16.9.8
Technical data
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v2
Table 793: L4UFCNTtechnical data
Function
Range or value
Accuracy
Counter value
0-65535
-
Max. count up speed
30 pulses/s (50% duty cycle)
-
16.10
Running hour-meter TEILGAPC
16.10.1
Identification
GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Running hour-meter
TEILGAPC
-
-
Section 16
1MRK 502 066-UUS B
Monitoring
1096
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...