![ABB Relion 670 series Technical Manual Download Page 1032](http://html.mh-extra.com/html/abb/relion-670-series/relion-670-series_technical-manual_30452261032.webp)
Name
Values (Range)
Unit
Step
Default
Description
V1AngRepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
V2HiHiLim
0.0 - 200.0
%VB
0.1
150.0
High High limit in % of UBase
V2HiLim
0.0 - 200.0
%VB
0.1
120.0
High limit in % of VBase
V2LowLim
0.0 - 200.0
%VB
0.1
80.0
Low limit in % of VBase
V2LowLowLim
0.0 - 200.0
%VB
0.1
60.0
Low Low limit in % of VBase
V2AngZeroDb
0 - 100000
m%
1
0
Zero point clamping in 0.001% of range
PID-3756-SETTINGS v5
Table 742: VNMMXU Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
VA_DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Operation
Disabled
Enabled
-
-
Disabled
Disbled/Enabled operation
VA_ZeroDb
0 - 100000
m%
1
1
Zero point clamping
VA_Max
0.0 - 200.0
%VB
0.1
200.0
Maximum value in % of VBase
VA_RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
VA_LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
VA_AnDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VB_DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VB_ZeroDb
0 - 100000
m%
1
1
Zero point clamping
VB_Max
0.0 - 200.0
%VB
0.1
200.0
Maximum value in % of VBase
VB_RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
VB_LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
VB_AnDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VC_DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VC_ZeroDb
0 - 100000
m%
1
1
Zero point clamping
VC_Max
0.0 - 200.0
%VB
0.1
200.0
Maximum value in % of VBase
Table continues on next page
Section 16
1MRK 502 066-UUS B
Monitoring
1026
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...