21.9.2
Function block
SEMOD55766-1 v2
SEMOD54868-4 v10
SMAI1
BLOCK
DFTSPFC
REVROT
^GRP1_A
^GRP1_B
^GRP1_C
^GRP1_N
SPFCOUT
G1AI3P
G1AI1
G1AI2
G1AI3
G1AI4
G1N
ANSI14000027-1-en.vsd
ANSI14000027 V1 EN-US
Figure 638: SMAI1 function block
Figure
is an example of SMAI1:n in each of the three task time groups 1, 2 or 3 where:
•
n=1–12 in task group 1
•
n=13–24 in task group 2
•
n=25–36 in task group 3
The task time defines the execution repetition rate, and is 1, 3 or 8 ms respectively for the three
task time groups.
SEMOD54997-4 v9
SMAI2
BLOCK
REVROT
^GRP2_A
^GRP2_B
^GRP2_C
^GRP2_N
G2AI3P
G2AI1
G2AI2
G2AI3
G2AI4
G2N
ANSI14000028-1-en.vsd
ANSI14000028 V1 EN-US
Figure 639: SMAI2 function block
Figure
is an example of SMAI2:n to SMAI12:m in each of the three task time groups 1, 2 or 3
where:
•
n=2 and m=12 in task group 1
•
n=14 and m=24 in task group 2
•
n=26 and m=36 in task group 3
The task time defines the execution repetition rate, and is 3, 8 or 1 ms respectively for the three
task time groups.
21.9.3
Signals
SEMOD55773-1 v2
PID-3405-INPUTSIGNALS v5
Table 981: SMAI1 Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block group 1
DFTSPFC
REAL
20.0
Number of samples per fundamental cycle used for DFT
calculation
REVROT
BOOLEAN
0
Reverse rotation group 1
GRP1_A
STRING
-
First analog input used for phase A or AB quantity
Table continues on next page
Section 21
1MRK 502 066-UUS B
Basic IED functions
1264
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...